Inspection History Details
Permit: T06EL01848
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/22/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1) MAIN BONDING SCREW IS STILL LOOSE-SEE SERVICE INSTRUCTIONS ON INTERIOR LABEL. SCREW IS TO TIGHT AND TORQUED TO 20-26 POUNDS. THIS IS CRITICAL FOR THE SAFE OPERATION OF THE SERVICE AND WAS CALLED FOR ON PREVIOUS INSPECTION 2) POWER WILL BE APPROVED AFTER ABOVE CORRECTION AND FINAL INSPECTION WILL BE MADE AFTER SERVICE IS ENERGIZED AND SWITCH OVER COMPLETE |
|
| 11/16/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* |
|
| 10/20/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK PARTIAL RACEWAY & BONDING COVER |
|
| 10/17/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WORK APPEARS INCOMPLETE. WHERE IS SERVICE LATERAL RACEWAY? HOW WILL NEW EQUIPMENT CKT TIE IN TO EQUIPMENT? HAVE SOMEONE ON SITE FOR INSPECTION WHO CAN ANSWER THESE QUESTIONS. |