Permit: T06EL01848


Addresses:

2451 N FAIRVIEW AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/28/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/22/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1) MAIN BONDING SCREW IS STILL LOOSE-SEE SERVICE INSTRUCTIONS ON INTERIOR LABEL. SCREW IS TO TIGHT AND TORQUED TO 20-26 POUNDS. THIS IS CRITICAL FOR THE SAFE OPERATION OF THE SERVICE AND WAS CALLED FOR ON PREVIOUS INSPECTION
2) POWER WILL BE APPROVED AFTER ABOVE CORRECTION AND FINAL INSPECTION WILL BE MADE AFTER SERVICE IS ENERGIZED AND SWITCH OVER COMPLETE
11/16/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
10/20/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
OK PARTIAL RACEWAY & BONDING COVER
10/17/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
WORK APPEARS INCOMPLETE. WHERE IS SERVICE LATERAL RACEWAY? HOW WILL NEW EQUIPMENT CKT TIE IN TO EQUIPMENT? HAVE SOMEONE ON SITE FOR INSPECTION WHO CAN ANSWER THESE QUESTIONS.