Permit: T06EL01845

Parcel: 106042150


Addresses:

3360 N FONTANA AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/05/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/02/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1) MOVE SERVICE CONDUCTORS TO OVER HEAD POSITION IN METER SECTION-NEC 110.3
2) WATER AND GAS BONDING CONDUCTOR IS UNDERSIZED-NEC 250.10
3) SYSTEM NEUTRAL NOT ALLOWED TO BOND EQUIPMENT ON LOAD SIDE OF SERVICE-NEC 250.142, 250.24 A 5
4) MAKE SURE PANEL DIRECTORY IS CORRECTLY IDENTIFIED AT FINAL-NEC 408.4