Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06EL01838
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HOW IS WATER & GAS BOND TIED TO SERVICE? 2. WHERE IS 2ND GROUND ROD? 3. HOW ARE FEEDERS RUN TO PANELS AND ARE EXISTING PANELS TO BE USED. 4. FITTING BETWEEN RISER & ENCLOSURE APPEARS TO HAVE A PLASTIC INTERIOR, THE HUB MUST BE OF A GROUND TYPE FOR UNPROTECTIVE CONDUCTORS 2002 NEC 250.92 |