| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) NOTE: INSTALL A HARD COVER OVER UNUSED METER SOCKET TO PREVENT ACCIDENTAL CONTACT |
|
| 10/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* NO INSPECTION MADE 1. NEED ELECTRICAL CONTRACTOR TO BE ON SITE TO OPEN EQUIPMENT AND PROVIDE ACCESS -- GATES ARE LOCKED ALSO, UNITS STILL SAY A,B,C? |
|
| 09/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. USE A LISTED GUY KIT OR STIFF ARMS FOR MAST BRACE - NEC 230.28 AND INSTALL SO IT WILL BRACE MAST IF THERE IS A PULL ON THE SERVICE LATERAL (EITHER IN FRONT OR BEHIND, NOT OFF TO SIDE). 2. DRIVE GROUND RODS FLUSH AND BURY GROUNDING ELECTRODE CONDUCTOR MINIMUM 12" NEC 250.53(G) 3. #6 GROUNDED CONDUCTOR TO BE IDENTIFIED PER NEC 200.6 4. INSTALL GUTTER THAT HAS NOT BEEN ALTERED (CUT) AND USE PROPER CONNECTORS FOR CABLES ENTERING GUTTER NEC 110.3 5. SERVICE NEEDS TO BE MOUNTED SECURELY TO WALL - NEC 110.13 6. PROVIDE STRAP FOR MAST -- NEC 344.30 7. BOND EACH UNITS WATER & GAS PIPING TO SERVICE AND TIGHTEN ALL BONDING CONNECTIONS NEC 250.104 8. BONDING CONDUCTORS FOR WATER AND GAS BOND IS UNDERSIZED -- NEC 250.104 (A) (1) 9. UNITS ARE "A" "B" "C" BUT YOU HAVE 1, 2, 3? |