Permit: T06EL01816

Parcel: 125070540


Addresses:

2601 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/13/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) NOTE TO CONTRACTOR ID MAIN PANEL PERMANENTLY "THIS SERVICE 3 DIAMETER 120/208 WITH HIGH LEG CPHASE, DO NOT USE CPHASE FOR 120V LOADS"
09/19/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK TO COVER TRENCH
09/12/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NEED MINIMUM 18" DEPTH FOR SERVICE CONDUCTORS OR CONCRETE ENCASEMENT -- NEC 300.5