Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) NOTE TO CONTRACTOR ID MAIN PANEL PERMANENTLY "THIS SERVICE 3 DIAMETER 120/208 WITH HIGH LEG CPHASE, DO NOT USE CPHASE FOR 120V LOADS" |
|
| 09/19/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO COVER TRENCH |
|
| 09/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED MINIMUM 18" DEPTH FOR SERVICE CONDUCTORS OR CONCRETE ENCASEMENT -- NEC 300.5 |