| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) ISOLATE NEUTRALS AND GROUNDS IN SUB PANEL |
|
| 03/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GROUND METAL 12 X 12 X 4 JB PER 250.4 AND SIZE GROUND WIRE PER 250.122 2) SPLIC CONDUCTORS IN 12 X 12 X 4 JB PER NEC 110.14 3) SECURE LIQUID TIGHT FLEX PER NEC 356.30 4) INSTALL ADDRESS LABEL 5) BOND WATER AND GAS LINE TO SERVICE 6) INSTALL BUSHING AT SEAL TITE TO PROTECT WIRES PER NEC 300.4 (F) |
|
| 02/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |