Permit: T06EL01771

Parcel: 114462120

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) SERVICE ONLY NEEDS TO BE SEALED
10/23/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CALL TO RESCHEDULE INSPECTION WITH RICK H.
09/25/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH PREVIOUS ITEMS.
09/21/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. GROUNDING ELECTRODE CONDUCTOR IN METAL RACEWAY TO BE BONDED AS PER 250.64
2. PLEASE UNCOVER GROUND RODS TO INSPECT CONNECTIONS.
3. BREAKERS TO BE LISTED FOR USE BY MANUFACTURER
4. WE HAVE EXTREME CORROSION ON MAIN BUSS
5. PLEASE VERIFY WATER BONDING
6. CANNOT TRIM CONDUCTORS
7. SUB-PANEL FEED IS A 2-WIRE SYSTEM NO GROUND.
8. NEED TO SEE CONNECTIONS TO INTERIOR SUB-PANEL
UNIT "A"
09/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED NO ACCESS