Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* NO FINAL APPROVAL UNTIL RECONNECT PERMIT OBTAINED AND INSPECTION APPROVED, UNIT MUST BE UP TO CODE. |
|
| 09/13/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* TRIED CALLING FROM 1PM TO 1:15 -- LINE BUSY 1. ALL CIRCUIT BREAKERS USED HAVE TO BE ITE LIKE MAIN. 2. NEED LOCK NUTS ON FITTING INSIDE SERVICES. 3. NEED TWO GROUND RODS SEPARATED BY 6' WITH A #4 COPPER GOING TO ONE SERVICE THEN YOU CAN TAP OUTSIDE TO GO TO OTHER . 4. BOARD ON WHICH SERVICES MOUNTED TO BE WEATHERPROOF. 5. MISSING DEAD FRONT COVERS TO BE ON FOR INSPECTION. *NOTE: ONCE SERVICES APPROVED POWER RELEASE TO UNITS WILL BE SUBJECT TO RECONNECT PERMITS & INSPECTIONS APPROVED FOR EACH. |