Permit: T06EL01730

Parcel: 11941248C


Addresses:

1701 W AJO WY #A

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/22/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
NO FINAL APPROVAL UNTIL RECONNECT PERMIT OBTAINED AND INSPECTION APPROVED, UNIT MUST BE UP TO CODE.
09/13/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
TRIED CALLING FROM 1PM TO 1:15 -- LINE BUSY

1. ALL CIRCUIT BREAKERS USED HAVE TO BE ITE LIKE MAIN.
2. NEED LOCK NUTS ON FITTING INSIDE SERVICES.
3. NEED TWO GROUND RODS SEPARATED BY 6' WITH A #4 COPPER GOING TO ONE SERVICE THEN YOU CAN TAP OUTSIDE TO GO TO OTHER .
4. BOARD ON WHICH SERVICES MOUNTED TO BE WEATHERPROOF.
5. MISSING DEAD FRONT COVERS TO BE ON FOR INSPECTION.

*NOTE: ONCE SERVICES APPROVED POWER RELEASE TO UNITS WILL BE SUBJECT TO RECONNECT PERMITS & INSPECTIONS APPROVED FOR EACH.