Permit: T06EL01725

Parcel: 125070340

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/01/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/30/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The service is not per code.| 210*
UNIT #1
1. NEED SEALING LOCKNUT ABOVE LINE PARTS IN PANEL
AND J-BOX
2. SELF TAP SCREW NOT ALLOWED FOR J-BOX GROUND
3. GROUNDING ELECTRODE CONDUCTOR TO BE SECURE TO BUILDING AND CAN'T BE RAN IN EMT UNLESS EMT IS MADE ELECTRICALLY CONTINUOUS.
4. BOND SERVICE TO WATER
5. DRIVE GROUND RODS FLUSH
6. CORRECTLY IDENTIFY PANEL DIRECTORY AND MAKE LEGIBLE
7. NEUTRALS AND GROUND SEPARATE IN SUB-PANEL
IF GROUND PATH EXIST TO SERVICE - PROVIDE INTERIOR ACCESS.

UNIT #2
1. PROVIDE CLEAR, UNOBSTRUCTED PATH TO SERVICE
2. DRIVE RODS FLUSH
3. SECURE G.E.C TO STRUCTURE OR BURY
4. BOND GAS PIPE