Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/30/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* UNIT #1 1. NEED SEALING LOCKNUT ABOVE LINE PARTS IN PANEL AND J-BOX 2. SELF TAP SCREW NOT ALLOWED FOR J-BOX GROUND 3. GROUNDING ELECTRODE CONDUCTOR TO BE SECURE TO BUILDING AND CAN'T BE RAN IN EMT UNLESS EMT IS MADE ELECTRICALLY CONTINUOUS. 4. BOND SERVICE TO WATER 5. DRIVE GROUND RODS FLUSH 6. CORRECTLY IDENTIFY PANEL DIRECTORY AND MAKE LEGIBLE 7. NEUTRALS AND GROUND SEPARATE IN SUB-PANEL IF GROUND PATH EXIST TO SERVICE - PROVIDE INTERIOR ACCESS. UNIT #2 1. PROVIDE CLEAR, UNOBSTRUCTED PATH TO SERVICE 2. DRIVE RODS FLUSH 3. SECURE G.E.C TO STRUCTURE OR BURY 4. BOND GAS PIPE |