Permit: T06EL01721

Parcel: 117033560


Addresses:

610 E UNIVERSITY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL01721

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/04/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. STILL NEED TO SECURE G.E.C & BOND WIRE TO STRUCTURE
2. PANEL DIRECTORY NOT LEGIBLE OR CORRECTLY IDENTIFIED SHOULD SAY CLEARLY WHAT BREAKER SERVES
I.E PORCH LIGHT

NOTE:
SECURE CONDUCTORS TO STRUCTURE SO THEY CAN'T BE PULLED AWAY AND USE STRAPS LISTED FOR #4 CU
REFEE WILL BE CHARGED IF NOT CORRECT NEXT INSPECTION
08/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE GAS BOND CONDUCTOR TO STRUCTURE.
2. SECURE AND OR BURY GROUNDING ELECTRODE CONDUCTOR.
3. TIGHTEN ALL ACORN/BOND CLAMPS
4. IDENTIFY WHITE CONDUCTOR USED AS HOT
5. PROVIDE PERMIT FOR ANY ADDED CKT'S - A.C?
6. NEED SEALING TYPE LOCKNUT FOR CONDUIT ENTRY ABOVE LIVE PARTS.
7. DO A BETTER JOB ON PANEL DIRECTORY -- WHAT IS "LT?"
WHAT IS "RECP"?