Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01695
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERIFY SIZE OF SERVICE CONDUCTORS. 2. MAST RACEWAY APPEARS TO BE OVERFILLED - NEC TABLE C8 3. MAST BOND UNDERSIZED - NEC 250.102C 4. BOND SERVICE GUTTER - NEC 250.92, 250.102C 5. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 B AS "SERVICE DISCONNECTS" 6. MOVE SERVICE CONDUCTORS TO OVERHEAD POSITION AS OUTLINED IN METER SECTIONS - NEC 110.3B 7. BURY GROUNDING ELECTRODE CONDUCTOR MINIMUM 12" BETWEEN GROUND RODS AND SECURE TO STRUCTURE INTO SERVICE - NEC 300.5, NEC 250.64B 8. IDENTIFY AC DISCONNECTS WITH SOMETHING SUITABLE FOR WEATHER - NOT A MARKER 9. J-BOXES NEED TO BE SECURED TO STRUCTURE - NEC 314.23 HAVE UNUSED OPENINGS FILLED - NEC 300.5 AND STRANDED NOT ALLOWED UNDERGROUND SCREW NEC 110 10. MAKE SURE YOU HAVE ALL METAL PIPES BONDED TO SERVICE THESE MAY HAVE SEPARATE WATER/GAS PIPING TO EACH UNIT - NEC 250.104 11. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES - NEC 358.30A |
|
12/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE EQUIPMENT OPEN FOR INSPECTION 2. TEP SEALS TO BE REMOVED ONLY WITH TEP AUTHORIZATION. 3. HAVE PLANS ON SITE. 4. NEED TO PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL |
|
12/08/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE EQUIPMENT OPEN FOR INSPECTION |
|
12/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GATES LOCKED, CONTRACTOR SAID GO TO MANAGER'S OFFICE NO ANSWER RECALL INSPECTION |
|
09/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TIGHTEN LOOSE FITTINGS 2. USE REDUCING WASHER WHERE CONCENTRICS ARE NOT COMPLETE. 3. VERIFY GROUND RODS 4. CONDUIT SUPPORTS TO BE ATTACHED TO STRUCTURE 5. MAINTAIN WORKING SPACES FOR A/C DISCONNECTS 110.26 6. WHITE CONDUCTORS FOR ENTIRE LENGTH ARE IDENTIFIED AS NEUTRAL CONDUCTORS NOT GROUNDING CONDUCTORS 200.7 7. LABEL BREAKERS 8. RAINTITE HUB TO BE LISTED FOR BONDING. 9. BOND DEVICES NEEDED FOR NIPPLES 10. ARRANGE CONDUCTORS SO AS TO ACCESS GUTTER. 11. LABEL A/C DISCONNECTS 12. OPEN SERVICE SIDE TO CHECK CONNECTION. TEP SEALED 13. PLEASE VERIFY PERMITS FOR NEW A/C UNITS. |