Permit: T06EL01695

Parcel: 117032890


Addresses:

730 N 6TH AV #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL01695

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/27/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VERIFY SIZE OF SERVICE CONDUCTORS.
2. MAST RACEWAY APPEARS TO BE OVERFILLED -
NEC TABLE C8
3. MAST BOND UNDERSIZED - NEC 250.102C
4. BOND SERVICE GUTTER - NEC 250.92, 250.102C
5. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 B AS "SERVICE DISCONNECTS"
6. MOVE SERVICE CONDUCTORS TO OVERHEAD POSITION AS OUTLINED IN METER SECTIONS - NEC 110.3B
7. BURY GROUNDING ELECTRODE CONDUCTOR MINIMUM 12" BETWEEN GROUND RODS AND SECURE TO STRUCTURE INTO SERVICE - NEC 300.5, NEC 250.64B
8. IDENTIFY AC DISCONNECTS WITH SOMETHING SUITABLE FOR WEATHER - NOT A MARKER
9. J-BOXES NEED TO BE SECURED TO STRUCTURE - NEC 314.23
HAVE UNUSED OPENINGS FILLED - NEC 300.5 AND STRANDED NOT ALLOWED UNDERGROUND SCREW NEC 110
10. MAKE SURE YOU HAVE ALL METAL PIPES BONDED TO SERVICE THESE MAY HAVE SEPARATE WATER/GAS PIPING TO EACH UNIT - NEC 250.104
11. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES -
NEC 358.30A
12/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE EQUIPMENT OPEN FOR INSPECTION
2. TEP SEALS TO BE REMOVED ONLY WITH TEP AUTHORIZATION.
3. HAVE PLANS ON SITE.
4. NEED TO PAY REINSPECTION FEE PRIOR TO FINAL APPROVAL
12/08/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE EQUIPMENT OPEN FOR INSPECTION
12/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GATES LOCKED, CONTRACTOR SAID GO TO MANAGER'S OFFICE
NO ANSWER
RECALL INSPECTION
09/14/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TIGHTEN LOOSE FITTINGS
2. USE REDUCING WASHER WHERE CONCENTRICS ARE NOT COMPLETE.
3. VERIFY GROUND RODS
4. CONDUIT SUPPORTS TO BE ATTACHED TO STRUCTURE
5. MAINTAIN WORKING SPACES FOR A/C DISCONNECTS 110.26
6. WHITE CONDUCTORS FOR ENTIRE LENGTH ARE
IDENTIFIED AS NEUTRAL CONDUCTORS NOT
GROUNDING CONDUCTORS 200.7
7. LABEL BREAKERS
8. RAINTITE HUB TO BE LISTED FOR BONDING.
9. BOND DEVICES NEEDED FOR NIPPLES
10. ARRANGE CONDUCTORS SO AS TO ACCESS GUTTER.
11. LABEL A/C DISCONNECTS
12. OPEN SERVICE SIDE TO CHECK CONNECTION. TEP SEALED
13. PLEASE VERIFY PERMITS FOR NEW A/C UNITS.