Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01688
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/07/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - KITCHEN COUNTERS TO BE GFI PROTECTED OUTLETS - OPEN GROUNDS/NEUTRALS IN LIVING & BEDROOMS BATHROOM |
|
07/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CONTRACTOR TO POWER CHECK, RECALL FOR FINAL WHEN DONE |
|
05/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEW WIRING TO INTERIOR 2. GROUNDING AT SERVICE INCORRECT 3. COVER TO SUB-PANEL MISSING 4. GROUNDING & NEUTRALS AT SUB-PANEL CONNECTED MUST BE SEPARATED 5. WIRING TO INSIDE WOULD NEED TO BE IN CONDUIT 6. IMPROPER BRACE KIT AT RISER |
|
04/26/2007 | ELECTRIC - FINAL | Denied | 1. ADDRESS SERVICE 2. (2) GROUND RODS & WATER & GAS BOND 3. USE A LISTED & APPROVED BRACE KIT ON RISER 4. STRAP #4 TO WALL 5. DRIVE GROUND RODS TO GRADE 6. RUN FEED TO PANEL LOCATION OBTAIN SERVICES OF A LICENSED CONTRACTOR |