Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* CALL FOR FINALS ONCE SERVICES SWITCHED OVER FOR FINALS DRIVE ALL GROUND RODS TO GRADE OR BELOW |
|
| 09/28/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. #6 SERVICE -- OFFSET/NIPPLE FROM METER TO PNL TO HAVE GROUND BUSHINGS, BECAUSE OK CONCENTRICS & UNPROTECTED WIRE) 2. #6 USE CUTLER HAMMER BREAKERS ONLY 3. #6 #4 COPPER TO RODS MUST GROUND NEUTRAL. 4. #9 OK TO CLEAR SERVICE UPGRADE |
|
| 09/15/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 08/29/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) NO NEW SERVICE UNIT #9 2) UNIT #6-INSTALL SERVICE WIRE, HOLDOWN KIT FOR MAIN, MAIN BONDING SCREW, BOND NIPPLE, BUSHING #4 AND LARGER CONDUCTORS, TIGHTEN BOND CLAMPS 3) UNIT #8-CAN'T FIND GROUND RODS 4) UNIT #7-ONLY SEE/ROD AND CLAMPS LOOSE 5) UNIT #5-INSTALL DEAD FRONT 6) GO THROUGH ALL AND TIGHTEN ALL BOND CLAMPS 7) UFERS TO GO TO NEW SERVICES 8) NO CLAMPS IN DIRECT CONTACT WITH EARTH (6" ABOVE) UNLESS LISTED |