Permit: T06EL01666

Parcel: 13339002B


Addresses:

10000 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL01666

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2006 ELECTRIC - FINAL Approved
08/23/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONDUIT ON ROOF NEEDS TO BE PROPERLY SUPPORTED.
2. EXTENSION CORD WIRING IS NOT ACCEPTABLE FOR FLOOR LIGHT AT CARPORT.
3. INSTALL N.M (ROMEX) CONNECTORS AT BOXES IN CARPORT & GFI PROTECT (OR REMOVE ALL TOGETHER)
4. REATTACH PORCELAIN PULL CHAIN FIXTURE (CARPORT WORK BENCH).
5. BBQ LIGHT IS NOT WIRED PROPERLY (PLEASE REMOVE WIRING FROM SOURCE)
6. OPEN SPLICE ABOVE EAST DOOR AT HOUSE.
7. CANOPY SHADE WIRING DOESN'T COMPLY WITH CODE.
8. ZIP CORD WIRING NOT ALLOWED AT N.WEST BEDROOM.
9. OPEN LAMP FIXTURE NOT ALLOWED IN CLOSET (HALL) 2 & BEDROOM CLOSETS.
10. LIVING ROOM SPOT LIGHT IS WIRED IN ZIP CORD THIS IS ILLEGAL.
11. INSTALL SMOKE DETECTORS IN HALL & ALL BEDROOMS AT LEAST 3' AWAY FROM ANY AIR REGISTER AND 6" - 12" FROM CEILING
12. BATH & KITCHEN & OUTDOOR RECEPTACLES TO BE GFCI PROTECTED WITH PROPER W.P COVERS OUTSIDE.