Permit: T06EL01662

Parcel: 115051040

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/25/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) NOTE: INSTALL PORCH LIGHT ON BOX
09/20/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
CORRECTIONS HAVE NOT BEEN COMPLETED -- DO NOT CALL
FOR FINAL BEFORE ALL CORRECTIONS HAVE BEEN PROPERLY COMPLETED OR REINSPECTION FEE WILL BE CHARGED.
09/18/2006 ELECTRIC - FINAL Denied 1. SAFE OFF OR REMOVE OPEN WIRING ON EXTERIOR
(WEST SIDE) OF HOUSE.
2. PROVIDE INTERIOR ACCESS.
09/15/2006 ELECTRIC - FINAL Denied 1. SUB-PANEL #12 WIRE COMING FROM INSIDE SERVICE -- WHAT IS IT FOR AND WHY IS THERE A CIRCUIT FROM THIS PANEL GOING TO UNIT #1 IF IT IS A BOX FOR FRONT.
2. HOT WATER HEATER WIRED IMPROPERLY
3. PNL NEEDS TO OPEN -- SEALED INTO WALL
4. OUTSIDE PORCH LIGHT CONNECTED IN ROMEX.
APPEARS TO BE AN UNPERMITTED ADDITION - HOWEVER, SOMEONE CLEARED FOR SERVICE TO BE ENERGIZED AT THIS BLDG.
08/24/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
UNIT NEEDS TO BE UNLOCKED FOR INSPECTION.
ALSO, SMOKE DETECTOR IN EACH ROOM AND HALLWAY
NO OPEN WIRING OR BROKEN DEVICES.