Permit: T06EL01660

Parcel: 123110490


Addresses:

1236 E LINDEN ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T06EL01660

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
10/23/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
09/19/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUND RODS TO BE AT LEAST 6 FEET APART.
2. BOND GAS AND WATER PIPES TO SERVICE
3. NEED SEALING LOCKNUT FOR SIDE ENTRY RACEWAY.
4. TIGHTEN ALL CONNECTIONS
5. MAX 15 AMP. ON 14ga WIRE
6. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE.
7. STRAP ALL EMT WITHIN 3' OF PANEL.