Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 09/19/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. GROUND RODS TO BE AT LEAST 6 FEET APART. 2. BOND GAS AND WATER PIPES TO SERVICE 3. NEED SEALING LOCKNUT FOR SIDE ENTRY RACEWAY. 4. TIGHTEN ALL CONNECTIONS 5. MAX 15 AMP. ON 14ga WIRE 6. SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE. 7. STRAP ALL EMT WITHIN 3' OF PANEL. |