Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* 1) DRIVE GROUND ROD DOWN TO GRADE 2) SWITCH GAS BOND TO HOUSE SIDE 3) CALL FOR FINAL WHEN CHANGE OVER COMPLETE |
|
| 08/25/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXPOSED GROUND RODS FOR INSPECTION 2. BOND WATER & GAS 3. #14 WIRE MUST BE ON 15 AMP. BREAKERS 4. LOCKNUTS GO INSIDE PANELS FOR 1 1/2" CONNECTORS 5. STRAP #4 BARE TO WALL. |