Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/21/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. IDENTIFY NEUTRAL CONDUCTOR CLOSER TO WEATHERHEAD 2. GUY BACK SUPPORT TO BE EFFECTIVE 3. PLEASE VERIFY DERATING OF CONDUCTOR 310.15 4. PROVIDE ACCESS TO CHECK GAS BOND 5. CLEAN SURFACE UNDER GROUND LUG 250.12 |