Permit: T06EL01647

Parcel: 132090130

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/20/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/16/2006 ELECTRIC - FINAL Partial Approval APPROVAL GIVEN ONLY FOR 3043 E. PROCTOR VISTA
ACTUAL ADDRESS IS 3043, CHANGE ON PERMIT TO REFLECT 3043 NOT 3049
OK TO CLEAR WHEN DONE
10/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. VERIFY WATER & GAS BOND
2. ADD 3043 TO PERMIT NOT 3049
3. BOND BUSHINGS OR LOCKNUTS REQUIRED IN GUTTER AHEAD OF OVERCURRENT.
4. EXTENSION BOX REQUIRED FOR BRANCH CIRCUITS.
5. THERE IS A VIOLATION PENDING AT THIS ADDRESS, NO POWER UNTIL CLEARED UP.
09/07/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. GROUNDING ELECTRODE SYSTEMS MUST BE TIED TOGETHER PER ART. 250 NEC FOR TWO SERVICES ON SAME STRUCTURE.
2. BOTH SYSTEM WIRING IN SAME J-BOX MUST HAVE CIRCUITS TAGGED AS TO DESIGNATE WHICH SERVICE.
3. NEED TO VERIFY GAS & WATER PIPE BONDING
4. WHY DO YOU ONLY HAVE 3041 ON PERMIT? WHAT ABOUT 3049?
5. I.D CIRCUIT BREAKERS IN PANELS
6. PROVIDE LADDER FOR GUTTER COVER REMOVAL AND INSPECTION