Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/16/2006 | ELECTRIC - FINAL | Partial Approval | APPROVAL GIVEN ONLY FOR 3043 E. PROCTOR VISTA ACTUAL ADDRESS IS 3043, CHANGE ON PERMIT TO REFLECT 3043 NOT 3049 OK TO CLEAR WHEN DONE |
|
| 10/05/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VERIFY WATER & GAS BOND 2. ADD 3043 TO PERMIT NOT 3049 3. BOND BUSHINGS OR LOCKNUTS REQUIRED IN GUTTER AHEAD OF OVERCURRENT. 4. EXTENSION BOX REQUIRED FOR BRANCH CIRCUITS. 5. THERE IS A VIOLATION PENDING AT THIS ADDRESS, NO POWER UNTIL CLEARED UP. |
|
| 09/07/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GROUNDING ELECTRODE SYSTEMS MUST BE TIED TOGETHER PER ART. 250 NEC FOR TWO SERVICES ON SAME STRUCTURE. 2. BOTH SYSTEM WIRING IN SAME J-BOX MUST HAVE CIRCUITS TAGGED AS TO DESIGNATE WHICH SERVICE. 3. NEED TO VERIFY GAS & WATER PIPE BONDING 4. WHY DO YOU ONLY HAVE 3041 ON PERMIT? WHAT ABOUT 3049? 5. I.D CIRCUIT BREAKERS IN PANELS 6. PROVIDE LADDER FOR GUTTER COVER REMOVAL AND INSPECTION |