Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE LISTED GUYBACK BRACES FOR RISER SUPPORT, HOMEMADE OUT OF SMASHED EMT CONDUIT NOT APPROVED. 2. DO NOT USE TOP SHIELDED AREA OF PANEL INTERIOR FOR LOAD CONDUIT OR BRANCH WIRING, SEE LISTING NOTES IN PANEL. 3. OPEN 6X6 J-BOX FOR INSPECTION -- BE SURE TO GROUND AND USE BOND BUSHINGS FOR TERMINATIONS USING RE-WASHERS. |