Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORY TO BE CORRECT & LEGIBLE - NEC 408.4 2. GROUNDS #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH - NEC 250.119 3. PROPERLY IDENTIFY SUB-PANEL NEUTRAL - NEC 200.6 (IT'S NOT A GROUND) 4. NEUTRAL #6 & SMALLER TO BE WHITE ENTIRE LENGTH - NEC 200.6 5. USE PROPER SIZE GROUNDS TO GROUND J-BOXES NEC 250.122 C 6. NEED PERMIT & INSPECTION FOR NEW AC & WATER HEATER 7. USE SEALING LOCKNUTS FOR SIDE ENTRY INTO ENCLOSURES - NEC 110, 312 |
|
| 03/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/23/2007 | ELECTRIC - FINAL | Cancelled |