Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/18/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WOOD SHOULD NOT BE USED FOR OUTDOOR SUPPORT OR CONDUIT PER 110-3 NEC 2. INSTALL 2" ROOF JACK AT RISER 3. INSTALL GROUNDING ELECTRODE SYSTEM 2 - 8'X5/8" GROUND RODS MIN. 6' APART. 4. INSTALL #4 WATER BOND 5. INSTALL #4 GAS BOND 6. ADDRESS LABEL IS WRONG 7. BRANCH CIRCUIT PANEL TOO HIGH BREAKERS CAN BE UTILIZED AT NEW PANEL. |