Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. EXPOSE BOTH GROUND RODS FOR INSPECTION 2. BOND GAS PIPING ON CUSTOMER SIDE OF METER, BOTH UNITS, ALSO WATER PIPING. 3. RISER CONDUIT ON 2311 NOT SCREWED INTO HUB. 4. BOND SERVICE GROUND ELECTRODE CONDUCTORS TOGETHER BELOW PANELS USING SPLIT BOLTS. |