Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL01608

Parcel: 13319155A


Addresses:

950 N CARIBE AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/05/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/01/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PRODUCT LABEL COMBUSTIBLE CURED FOAM ABOVE 240 DEG. F
08/29/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TO CLEAR INCR RESD CALLED MAP ROOM 5:38 PM
1. SEPARATE GROUNDING EQUIPMENT CONDUCTORS
2. SIZE BONDING JUMPER FOR SERVICE CONDUCTORS
PER 250.66
3. PRODUCT USED TO FILL UNUSED PORTION TO BE NON-COMBUSTIBLE.
4. LABEL BREAKERS
5. SUPPORT CONDUIT BELOW PANEL
6. USE AN ANTI-OXIDE COMPOUND WITH ALUMINUM CONDUCTORS.
08/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SERVICE NOT DONE AT THIS TIME