Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PRODUCT LABEL COMBUSTIBLE CURED FOAM ABOVE 240 DEG. F |
|
| 08/29/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR INCR RESD CALLED MAP ROOM 5:38 PM 1. SEPARATE GROUNDING EQUIPMENT CONDUCTORS 2. SIZE BONDING JUMPER FOR SERVICE CONDUCTORS PER 250.66 3. PRODUCT USED TO FILL UNUSED PORTION TO BE NON-COMBUSTIBLE. 4. LABEL BREAKERS 5. SUPPORT CONDUIT BELOW PANEL 6. USE AN ANTI-OXIDE COMPOUND WITH ALUMINUM CONDUCTORS. |
|
| 08/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SERVICE NOT DONE AT THIS TIME |