Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01603
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2006 | ELECTRIC - FINAL | Approved | ||
08/18/2006 | ELECTRIC - FINAL | Denied | ROMEX NOT ALLOWED TO BE USED OUTDOORS OR TO HOOK UP A MH, AS REQUESTED PRIOR. USE A LISTED MH CORD WITH A PERMANENT MOLDED CAP | |
08/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED TO USE A LISTED POWER CORD OR PERMANENTLY INSTALLED FEEDER IN A COMPLETE RACEWAY. NEC 550.10 USE A QUALIFIED ELECTRICIAN |
|
08/16/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE PROPER CORD TO HOOK UP MOBILE HOME AND MAKE SURE FEEDER CONDUCTORS TO HOME PANEL ARE PROTECTED BY THE PROPER SIZE BREAKER FDR THEIR AMPACITY. 2. REMOVE/REPAIR ALL OPEN WIRING 3. REMOVE LIGHT IN SHOWER OR USE LISTED SHOWER FIXTURE/TRIM |