Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NO COMPLIANCE WITH NOTE #2 AT END ON CONDUIT WHERE ROMEX EXITS EMT UNDER ROOF OVERHANG. 2. SHEETMETAL SCREWS NOT ALLOWED TO FASTEN GROUND LUG TO J-BOX, USE THREADED BOLT WITH NUT. PER 250 NEC 3. SUPPORT OR STRAP #8 BARE TO WALL OF HOUSE. |
|
| 08/18/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ROOF JACK ON RISER CONDUIT AT ROOF PENETRATION. 2. INSTALL BUSHINGS AT END OF EMT WHERE ROMEX EXITS CONDUIT. 3. GROUND 6X6 J-BOX |