Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 08/15/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. GROUND WIRE DID NOT MAKE IT INTO TERMINAL AT SERVICE. 2. NEED A SEALING LOCK NUT FOR #2 ABOVE. |
|
| 08/10/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. GROUNDING ELECTRODE TO BE AS CLOSE AS POSSIBLE 250.30 2. SEAL ENTRANCE ABOVE CURRENT CARRING PARTS WITH AN APPROVED FITTING OR DEVICE. 3. RISER HARDWARE TO BE 1/4" MINIMUM 4. HOUSE IS VACANT - MAKE LOAD SIDE CONNECTIONS 5. BOND AROUND VALVES & UNIONS TO INTERIOR PIPING 6. BRACE SUPPORTS TO BE EFFECTIVE |