Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2006 | ELECTRIC - FINAL | Approved | ||
| 09/25/2006 | ELECTRIC - FINAL | Denied | 1) MULTIPLE CONNECTIONS NOT ALLOWED ON ONE LUG 2) INSTALL ADDRESS LABEL ON SERVICE 3) BOND BUSHING REQUIRED ON 2" NIPPLE 4) BOND NEUTRAL IN PANEL |
|
| 09/12/2006 | ELECTRIC - FINAL | Denied | NOTE: 1. NEW SERVICE GROUND SYSTEM ALSO TO WATER & GAS PIPING. 2. SEE NOTE #3 INSP. 8/10/06 3. COMPLETE WIRING TO NEW SERVICE. |