Date Description Inspector Results Comments
10/02/2006 ELECTRIC - FINAL Approved
09/25/2006 ELECTRIC - FINAL Denied 1) MULTIPLE CONNECTIONS NOT ALLOWED ON ONE LUG
2) INSTALL ADDRESS LABEL ON SERVICE
3) BOND BUSHING REQUIRED ON 2" NIPPLE
4) BOND NEUTRAL IN PANEL
09/12/2006 ELECTRIC - FINAL Denied NOTE:
1. NEW SERVICE GROUND SYSTEM ALSO TO WATER & GAS PIPING.
2. SEE NOTE #3 INSP. 8/10/06
3. COMPLETE WIRING TO NEW SERVICE.