Permit: T06EL01566

Parcel: 120080920


Addresses:

4517 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
09/15/2006 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
09/12/2006 ELECTRIC - RECONNECT Denied
08/17/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PREMESIS STILL HAS WIRING NOT TO CODE.
2. COOLER WIRING ON ROOF IS EXPOSED, NO W/P BOX
3. SERVICE PANEL COVER NOT THE RIGHT BRAND, DOES NOT OPEN & CLOSE PROPERLY, ALSO DEAD FRONT MISSING.
4. MISMATCH BREAKERS IN PANEL, MUST BE ALL OF SAME AS PANEL MANUFACTURER, NEUTRAL WIRE FROM METER SHOULD BE WHITE NOT GREEN.
5. CONDUITS FROM SERVICE PANEL TO BLD. NOT SUPPORTED PER CODE.
08/10/2006 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WALL BUILT AROUND SERVICE - PANEL DOOR MUST OPEN COMPLETELY. MUST HAVE 36" IN FRONT 30" WIDE DEDICATED ELECTRICAL & WORKING SPACE. PER NEC 110.26
2. EXPOSED ROMEX, CABLES THROUGHOUT
PLASTIC DEVICE BOXES NOT PROPER APPLICATION. EXPOSED WIRING.
3. IF CARS - AUTOS TO BE SERVICED THE BUILDING MUST COMPLY WITH ART. 511 NEC

OBTAIN SERVICES OF A LICENSED CONTR. OR QUALIFIED ELECTRICAL TO MAKE REPAIRS TO COMPLY WITH 2002 NEC HAVE CONTRACTOR CALL INSPECTOR WHEN READY.
791-5550 EXT. 1136 RAY M. OR DAN SANTA CRUZ

ALSO, CHECK OUT ROOF WIRING,
HAVE LADDER ON SITE NEXT INSP.