Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS INSPECTION ITEMS 2. PLEASE PROVIDE A LETTER FROM THE TESTING LAB AND THE MANUFACTURER VERIFYING USAGE AS INSTALLED. |
|
| 08/24/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CANNOT FORK CONDUCTORS 2. TIGHTEN LOOSE FITTINGS A/C & WATER HEATER 3. WILL MEET WITH SENIOR ELECTRICAL INSPECTOR TO REVIEW PANEL LISTING. |
|
| 08/07/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE VERIFY GAS BOND. 2. NO ENTRANCES THROUGH METER SECTION PER MANUFACTURER. 3. INSTALL ALL STRANDS OF CONDUCTOR UNDER TERMINAL LUG. 4. NEED ACCESS TO NEW SUB-PANEL 5. PLEASE ADD NEW SUB-PANEL AND NEW CIRCUITS TO PERMIT - DRYER, WASHER, WATER HEATER, AC 6. PLEASE VERIFY NEW PERMIT FOR NEW A/C |