Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL01517
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/19/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES 1. INSTALL BOND BUSHING AT CONCENTRIC KO 1 1/2" TERM. 2. WHY ARE THERE 2 #6 WHITE FEEDERS, IF ONE IS A GROUND IT MUST BE GREEN. PER NEC 3. BOND WATER & GAS PIPING 4. BOLTS FOR RISER CONDUIT MUST BE 1/4" MIN. |
|
| 10/18/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : There is no access to the site.| 920* DOGS IN YARD - NO ANSWER AT FRONT DOOR RECALL INSPECTION LOCK UP DOGS |