Permit: T06EL01517

Parcel: 120085550


Addresses:

250 W KENTUCKY ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/16/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/19/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES
1. INSTALL BOND BUSHING AT CONCENTRIC KO 1 1/2" TERM.
2. WHY ARE THERE 2 #6 WHITE FEEDERS, IF ONE IS A GROUND IT MUST BE GREEN. PER NEC
3. BOND WATER & GAS PIPING
4. BOLTS FOR RISER CONDUIT MUST BE 1/4" MIN.
10/18/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
There is no access to the site.| 920*
DOGS IN YARD - NO ANSWER AT FRONT DOOR
RECALL INSPECTION LOCK UP DOGS