Permit: T06EL01515

Parcel: 133243700

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
08/14/2006 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
08/11/2006 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
LOCKED NO ACCESS
08/05/2006 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
1. PLEASE VERIFY THAT WIRING IN PATIENT CARE AREAS MEET THE REQUIREMENT OF 517.15(A) & (B)
2. WE HAVE OPEN WIRING AND PANEL IN A ROOM.
3. FILL UNUSED OPENING IN BOTTOM OF MAIN DISCONNECT.
4. SERVICE IS MISSING GROUNDING ELECTRODE CONDUCTOR.
5. REVISE PANEL SCHEDULE TO VERIFY AREAS.