Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 08/11/2006 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* LOCKED NO ACCESS |
|
| 08/05/2006 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE VERIFY THAT WIRING IN PATIENT CARE AREAS MEET THE REQUIREMENT OF 517.15(A) & (B) 2. WE HAVE OPEN WIRING AND PANEL IN A ROOM. 3. FILL UNUSED OPENING IN BOTTOM OF MAIN DISCONNECT. 4. SERVICE IS MISSING GROUNDING ELECTRODE CONDUCTOR. 5. REVISE PANEL SCHEDULE TO VERIFY AREAS. |