Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T06EL01506
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CALL IN BOTH UNITS AT ONCE SO BOTH CAN BE CLEARED 2. THE BRACING SYSTEM FOR RISERS IS INSUFFICIENT, USE APPROVED BRACING KIT FOR EACH CONDUIT. 3. EACH BUILDING SINCE THEY ARE INDIVIDUAL IS REQUIRED TO HAVE ITS OWN GROUND SYSTEM PLUS WATER AND GAS BONDS UNLESS NON METALLIC 4. EXPOSE CONNECTIONS ON GROUND ROD 5. CONDUIT ABOVE PANEL ON UNIT #1 HAS TO BE SUPPORTED WITHIN 3' OF ENCLOSURE 6. PROVIDE ROOF ACCESS 7. IF SERVICES ON UNIT #2 TO SHARE GROUND SYSTEM MAKE TOP OUTSIDE OF ENCLOSURES |