Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06EL01499

Parcel: 12112437A


Addresses:

5452 E BELLEVUE ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06EL01499

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/21/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/17/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED PERMANENT ADDRESS LABELS
2) NEUTRAL/GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH 200.7
3) PRODUCT TO FILL UNUSED PORTION TO BE NON COMBUSTIBLE
4) RECALL BY 8/21/06
5) RECEIVED CHECK #1545 FOR $108.00
08/17/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOND ALL GAS TO INTERIOR PIPING
2. BOND WATER
3. REPAIR AERIAL CONNECTIONS AT 1ST BUILDING
4. AERIAL CONDUCTORS IN DETERIORATED CONDITION.
5. WE HAVE A TAP IN VIOLATION AT 2ND BUILDING
6. BOND JUNCTION BOX ENCLOSURE
7. SUPPORT CONDUIT ALONG SIDE OF METER PACK