Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/17/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED PERMANENT ADDRESS LABELS 2) NEUTRAL/GROUNDED CONDUCTOR TO BE WHITE ENTIRE LENGTH 200.7 3) PRODUCT TO FILL UNUSED PORTION TO BE NON COMBUSTIBLE 4) RECALL BY 8/21/06 5) RECEIVED CHECK #1545 FOR $108.00 |
|
08/17/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOND ALL GAS TO INTERIOR PIPING 2. BOND WATER 3. REPAIR AERIAL CONNECTIONS AT 1ST BUILDING 4. AERIAL CONDUCTORS IN DETERIORATED CONDITION. 5. WE HAVE A TAP IN VIOLATION AT 2ND BUILDING 6. BOND JUNCTION BOX ENCLOSURE 7. SUPPORT CONDUIT ALONG SIDE OF METER PACK |