Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/25/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK TO COVER |
|
| 09/20/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* (BACK SLIDING DOOR OPEN) 1. OK TO COVER COUNTER WALLS AND WEST WALL NORTH OF SINK. 2. NOT OK TO COVER ROMEX WIRING GOING UP WEST WALL INTO ATTIC, HOW WILL THESE BE PHYSICALLY PROTECTED? THERE IS NO INDICATION HOW THESE WILL BE COVERED. |
|
| 09/19/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* BACK DOOR OPEN PER MESSAGE 9:20 AM -- FRONT & REAR DOORS LOCKED |
|
| 08/28/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DENIED BECAUSE OF GROUND INSTALLATION CANNOT BE BEND AND MUST GO STRAIGHT DOWN OR FOLLOW EXCEPTIONS IN CODE. 2. TAPE NEUTRAL USED AS HOT 3. FILL OUT SCHEDULE PERMANENTLY --- NO PENCIL 4. WHERE IS WATER AND GAS BOND? |
|
| 08/08/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |