Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/13/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* MADE 3 ATTEMPTS TO THE CELL # ON THE MESSAGE -- NO ANSWER NO VOICEMAIL. 1. JUNCTION BOX IS NEEDED. OLD PANEL IS NOT BIG ENOUGH FOR ALL CONDUCTORS. BOX NOT SEALABLE AS A JUNCTION BOX. BOX IS SURFACE MOUNTED & ABLE TO BE CHANGED. |
|
| 09/26/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1. LABEL CIRCUIT BREAKERS 2. USE CORRECT SIZED JUNCTION BOX FOR CONDUCTORS 3. GROUND BAR -- SHEET METAL SCREWS NOT ALLOWED, CLEAN SURFACE UNDER BAR. 4. TIGHTEN LOOSE FITTINGS. 5. TERMINATE ALL CONDUCTORS 6. NO METALLIC RACEWAY NEED GROUNDING CONDUCTOR 7. DO NOT FORK OR SPLIT CONDUCTORS. |