Permit: T06EL01496

Parcel: 126010480


Addresses:

106 N IRVING AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/27/2007 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/13/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
MADE 3 ATTEMPTS TO THE CELL # ON THE MESSAGE --
NO ANSWER NO VOICEMAIL.

1. JUNCTION BOX IS NEEDED. OLD PANEL IS NOT BIG ENOUGH FOR ALL CONDUCTORS. BOX NOT SEALABLE AS A JUNCTION BOX. BOX IS SURFACE MOUNTED & ABLE TO BE CHANGED.
09/26/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
1. LABEL CIRCUIT BREAKERS
2. USE CORRECT SIZED JUNCTION BOX FOR CONDUCTORS
3. GROUND BAR -- SHEET METAL SCREWS NOT ALLOWED, CLEAN SURFACE UNDER BAR.
4. TIGHTEN LOOSE FITTINGS.
5. TERMINATE ALL CONDUCTORS
6. NO METALLIC RACEWAY NEED GROUNDING CONDUCTOR
7. DO NOT FORK OR SPLIT CONDUCTORS.