Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 10/19/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND SERVICE RISER -- NEC 250.92, USE PROPER SIZE BONDING CONDUCTOR -- NEC 250.102 2. BOND ALL METAL PIPING SYSTEMS TO SERVICE -NEC 250.104 3. IDENTIFYING SERVICE DISCONNECT -- NEC 250.70 (B) 4. TERMINATE GROUNDING ELECTRODE CONDUCTOR 5. IDENTIFY NEUTRALS IN GUTTER -- NEC 200 |
|
| 10/12/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | OK TO COVER 90 DEG. BELOW SERVICE |