Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06EL01483

Parcel: 130052530


Addresses:

2329 S CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/05/2006 ELECTRIC - SERVICE UPGRADE Approved
08/10/2006 ELECTRIC - SERVICE UPGRADE Partial Approval CALL FOR FINAL AFTER TEP TIE IN
08/08/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
2329
1. SEE NOTES 2331 - BOND WATER & GAS PIPING.
2. BOND SERVICE GROUND ELECTRODES TOGETHER.
2331
1. BOND WATER & GAS PIPING
2. INSTALL #4 JUMPER BETWEEN #4 GROUNDING ELECTRODE CONDUCTOR EACH SERVICE, SPLIT BOLT OK PER 250 NEC.
08/02/2006 ELECTRIC - SERVICE UPGRADE Cancelled IVRS - RI canceled