Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2006 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 08/10/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | CALL FOR FINAL AFTER TEP TIE IN | |
| 08/08/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 2329 1. SEE NOTES 2331 - BOND WATER & GAS PIPING. 2. BOND SERVICE GROUND ELECTRODES TOGETHER. 2331 1. BOND WATER & GAS PIPING 2. INSTALL #4 JUMPER BETWEEN #4 GROUNDING ELECTRODE CONDUCTOR EACH SERVICE, SPLIT BOLT OK PER 250 NEC. |
|
| 08/02/2006 | ELECTRIC - SERVICE UPGRADE | Cancelled | IVRS - RI canceled |