Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/01/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GAS BONDS & WATER TO BE TO INTERIOR SIDE PIPING OF ALL UNITS. 2. FINISH FANS. |
|
| 08/08/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FAN NEEDS J-BOX 2. HANGING FIXTURE CANNOT HAVE EXTENSION CORD 3. ALL PLUGS MUST BE PROPERLY GROUNDED IF UTILIZING GROUNDING TYPE RECEPTACLES OR REPLACE WITH NON-GROUNDING RECEPTACLES. 4. GROUNDING ELECTRODE CONDUCTOR, WATER & GAS BOND HAS BEEN CUT FROM THE ELECTRIC SERVICE. 5. DIDN'T LOCATE SUB-PANEL TENANT NEEDS ACCESS TO THEIR OVERCURRENT PROTECTION (BREAKERS) |