Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WE HAVE GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM. 2. A SMOKE DETECTOR IS NEEDED 3. SUPPORT CONDUIT FROM PANEL 4. TIGHTEN LOOSE LOCKNUTS 5. WE HAVE MULTIPLE TERMINATION AT MAIN LUG 6. A PERMANENT ADDRESS LABEL IS NEEDED 7. MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE. |