Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/28/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SECURE DOG AND HAVE GATE UNLOCKED FOR INSPECTION |
|
| 07/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. THIS PANEL IS LABELED FOR UNDERGROUND SERVICE ONLY ALSO, BOND CLAMP SCREWS ARE LOOSE SERVICE MAST NOT BONDED PANEL DIRECTORY NOT IDENTIFIED HAVE OPEN BREAKER SPACES COULD NOT OPEN DEADFRONT ONLY ONE GROUND ROD? USE LISTED OVERHEAD SERVICE |