Permit: T06EL01457

Parcel: 133250740


Addresses:

8641 E COLETTE ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
CONTRACTORS SCOPE OF WORK IS COMPLETE
FINAL SUBJECT TO PERMIT # FOR MECHANICAL
08/03/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE
2. PLEASE FILL UNUSED PORTION OF ENTRANCE IN BACK OF PANEL WITH A NEW COMBUSTIBLE PRODUCT -- CABLE SHEATHING TO EXTEND 1/4" INTO PANEL.
3. USE APPROVED PVC GLUE
4. NM CABLE NOT LISTED FOR DIRECT BURIAL OR UNCOVER NEW CONDUCT TO INSPECT
5. PHONE CABLE NOT ALLOWED IN RACEWAY UNLESS LISTED 300V
6. WHY A 30AMP CIRCUIT FOR SHOP LIGHTS?
7. PLEASE VERIFY NEW PERMIT FOR NEW A/C
8. LABEL ALL BREAKERS