Permit: T06EL01444

Parcel: 141091730

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
12/13/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
12/07/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLAN CALLS FOR 12 GAUGE WIRE -- 14 GAUGE USED
2. PLAN CALLS FOR 20 AMP GFCI BREAKER -- NOT INSTALLED
3. LABEL PANEL FOR THIS CIRCUIT