Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06EL01441
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
12/07/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR 12-2 WIRE 14-2 USED 2. 20 AMP CB CANNOT BE ON 14-2 WIRE 3. PLAN CALLS FOR 20 AMP GFCI BREAKER -- NOT INSTALLED 4. NMC CABLE NOT ALLOWED IN CONDUIT |