Permit: T06EL01441

Parcel: 141091760

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06EL01441

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
12/13/2006 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
12/07/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLAN CALLS FOR 12-2 WIRE
14-2 USED
2. 20 AMP CB CANNOT BE ON 14-2 WIRE
3. PLAN CALLS FOR 20 AMP GFCI BREAKER -- NOT INSTALLED
4. NMC CABLE NOT ALLOWED IN CONDUIT