Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01434
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/13/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
12/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR #12 WIRES -- #14 USED 2. PLAN CALLS FOR 20 AMP GFCI BREAKER NOT INSTALLED 3. LABEL THIS CIRCUIT IN PANEL 4. EXPOSE ALL WIRES IN THIS CIRCUIT FOR INSPECTION 5. FILL OPEN KNOCK OUT IN "J" BOX |