Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2006 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 07/28/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ALL INTERIOR DEVICE COVERS 2. REPAIR OR REPLACE ANY CRACKED DEVICES OR COVERS 3. ON EXTERIOR AT SERVICE - INSTALL L.B COVER, INSTALL BLANKS ON UNUSED ENCLOSURE OPENINGS AT DISCONNECT AND PANEL. REPAIR LOOSE BONDING CONNECTION IN SERVICE DISCONNECT. IDENTIFY ADDRESS ON SERVICE DISCONNECT. HAVE DOUBLE TAP ON LOAD SIDE OF DISCONNECT THAT OCCUPY SAME RACEWAY AS SERVICE CONDUCTORS? |
|
| 07/27/2006 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : There is no access to the site.| 920* NEED TO PROVIDE INTERIOR ACCESS NO REPLY @ MESSAGE PHONE |