Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/04/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DOESN'T HAVE THE REQUIRED WORKING CLEARANCE 2. EXPOSED ROMEX IS NOT ALLOWED 3. SEAL ALL UNUSED OPENINGS IN ELEC. PANEL 4. INSTALL ANTI-OXIDATION PASTE ON ALL ALUM. TERMINATIONS. 5. INSTALL LOCKNUT ON 1" PVC MALE ADAPTER 6. EXPOSE U.F CABLE IS NOT ALLOWED PER N.E.C 7. OPEN CONDUCTORS NOT ACCEPTABLE BEHIND ELEC. PANEL 8. PER T.E.P INSTALL METAL ADDRESS TAG 9. USE ONLY SQ D BREAKERS IN THIS PANEL. 10. BOND INTERIOR GAS PIPING PER ART. 250 11. WOOD NOT ACCEPTABLE FOR MOUNTING SERVICE (ATTACH DIRECTLY TO MASONRY) 12. J-BOX IS OVERFILLED 13. INSTALL BUBBLE COVER (IN USE COVER) AT GFCI RECEPTACLE. 14. SPLICE IS NT ACCEPTABLE BEHIND PANEL 15. #10 COPPER IS NOT CAPABLE OF 40 AMPS. CHANGE BREAKER TO 30 AMP. 16. LABLE PANEL. 17. GROUND AC UNIT |
|
| 08/02/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* NOTE: MAINTAIN OR MAKE REQUIRED WORKING CLEARANCE AT SERVICE & PANEL (WATER PIPING IS IN THE WAY) ANY QUESTIONS 954-0161 BOB SUBA |