Permit: T06EL01416

Parcel: 134181060


Addresses:

7402 E PLACITA MONO

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/08/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/04/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DOESN'T HAVE THE REQUIRED WORKING CLEARANCE
2. EXPOSED ROMEX IS NOT ALLOWED
3. SEAL ALL UNUSED OPENINGS IN ELEC. PANEL
4. INSTALL ANTI-OXIDATION PASTE ON ALL ALUM. TERMINATIONS.
5. INSTALL LOCKNUT ON 1" PVC MALE ADAPTER
6. EXPOSE U.F CABLE IS NOT ALLOWED PER N.E.C
7. OPEN CONDUCTORS NOT ACCEPTABLE BEHIND ELEC. PANEL
8. PER T.E.P INSTALL METAL ADDRESS TAG
9. USE ONLY SQ D BREAKERS IN THIS PANEL.
10. BOND INTERIOR GAS PIPING PER ART. 250
11. WOOD NOT ACCEPTABLE FOR MOUNTING SERVICE (ATTACH DIRECTLY TO MASONRY)
12. J-BOX IS OVERFILLED
13. INSTALL BUBBLE COVER (IN USE COVER) AT GFCI RECEPTACLE.
14. SPLICE IS NT ACCEPTABLE BEHIND PANEL
15. #10 COPPER IS NOT CAPABLE OF 40 AMPS. CHANGE BREAKER TO 30 AMP.
16. LABLE PANEL.
17. GROUND AC UNIT
08/02/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
NOTE: MAINTAIN OR MAKE REQUIRED WORKING CLEARANCE AT SERVICE & PANEL (WATER PIPING IS IN THE WAY)
ANY QUESTIONS 954-0161 BOB SUBA