Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTE: #2 VERIFY WATER BOND |
|
| 11/03/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT #BARE TO WALL AT GAS PIPE BOND. 2. VERIFY WATER PIPE BOND. 3. EMT CONNECTOR NOT PROPER METHOD TO TERMINATE LB INTO SIDE OF PANEL. ALSO, CHASE NIPPLE NOT APPROVED. USE CLOSE NIPPLES WITH LOCKNUTS BOTH SIDES OF PANEL USE SEALING LOCKNUT ON RIGHT SIDE. 4. EXPOSE GROUND RODS. |
|
| 07/25/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |