Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 08/07/2006 | ELECTRIC - CABLE DROP | Partial Approval | ||
| 07/31/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service is not per code.| 210* 1. NEW SERVICES NEEDS GROUND RODS 2. BOND OLD GROUNDING ELECTRODE TO SERVICES 3. BOND ALL METAL PIPING TO SERVICES 4. SEAL TOP OF DEAD MAN MAST (COUPLING & SCREW IN KO) |