Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T06EL01402
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. TIGHTEN LOOSE LOCKNUT 2. SUPPORT CONDUIT BELOW PANEL 3. PROTECT CONDUIT FROM CORROSION 4. IS NM CABLE BURIED OR FULL RACEWAY SYSTEM. IF BURIED IT MUST BE "UF" 5. FITTING TO BE LISTED FOR OUTDOOR USES 6. ARE BOXES FAN RATED 7. FILL UNUSED PORTION IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT. 8. LABEL ALL BREAKERS 9. PLEASE ADD NEW CIRCUITS TO PERMIT 10. IS NEW 12-3 A MULTI CORE CIRCUIT 11. PLEASE VERIFY LOADS FOR 2 CONDUCTOR TO 1 BREAKER 12. FILL UNUSED OPENINGS IN PANEL DEAD FRONT 13. BREAKER AMPACITY TO BE SIZE PER CONDUCTORS. |